Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Click here to ask your question

Ignition and pump run when cold water taps are turned off?

Re: Vaillant ecoTEC Plus 831 Condensing Boiler.

Ignition and pump run when cold water taps are turned off.

All functions are working alright except that when the cold taps are run, the boiler fires up momentarily when the cold tap is turned off, then powers down with the pump overrun. What could be the cause of this and what is the solution to remedy.
Edward, September 2012
Have you had any recent changes to your water pipework? The common cause of this is a 'dead leg' in the water pipework.
Think and check.
The other way of sorting this out is to install a non-return valve on to the cold water pipework in to the boiler.

Carefree, September 2012