Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

loud bang when boiler fires up, fault code F1 if it fails to fire?

Glow Worm flexicom 30 SX
Our boiler is just over two years old. It often fires up totally normally but sometimes this is preceeded by a loud bang through the flu duct presumably as the gas ignites, although a local boiler engineer thought the bang was before the flame ignited. Is this possible. If it fails to light, then a fault code F1 is displayed. Pressing the reset button clears this and the boiler will then ignite either with or without the loud bang.
Malc, December 2012
Did you get your boiler fixed? My boiler is only 3 weeks old and started doing the same

Jake, November 2014
Flexicom f1 noisy ignition is usually electrode bent , or cracked ( sparks in wrong place and then. Bang. Change electrode.

Oops, December 2012
dust in main burner, needs taking out and washing in soap and water the bang will then be gone

james morris, December 2012