Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    Click here to ask your question

how do i stop my overflow or pressure pipe from dripping?

I have a ferroli medina 102 and the pressure pipe ( or overflow pipe keeps dripping) the boiler is working fine and I have the water pressure set at 1 bar I have fitted a new water pressure valve part No. 30905920. but it is still leaking. Please can you help
Stan J., November 2013
When you the start boiler from cold does the pressure rise to 3 bar if so the expansion vessel may need pumping back up,otherwise is it the condensate drain that you are looking at in which case it's doing its job

toptrish, November 2013