David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    John asked ... How can I mend my binatone veva 1210 handset?    |    Click here to ask your question

Baxi 105 e ?

Can anyone tell me why the needle on pressure gauge risers when the central heating is put on ? I can only put heating on low to keep it at 2 on pressure gauge. Would be grateful if anyone has any ideas before calling an engineer ,
Sarah, February 2016
If the pressure is between 1 & 1.25 when the system is cold and the rises rapidly ( within 20 mins ) to 3 bar then there is a problem with the expansion vessel. If this is the case then you should get a registered engineer to address the problem

Mac, February 2016
When this happened to my Worcester condensor boiler i was advised to let more water into the system,this worked for me

James, February 2016
Water in the sealed system gets hot, expands, increasing the pressure in the system.

Check you have the correct pressure with the system cold.

RTFM, February 2016