59 mins ago Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

why do I have to pressurising my boiler?

I have to keep pressurising my potterton promax combi 28 he plus, Can anyone help?
Amanda, January 2017
The reason for constant repressuring, 1,loosing water ie leaking radiator,or 2,faulty pressure relief valve,or more likely 3, faulty expansion vesell. water will be dripping from the outside pipe in the latter 2 situations.

Name ron homer, heating engineer. wolverhampton, February 2017