1 hour ago Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

Scantronic 9751 Aux DC Fail keep blowing fuses?

Have replaced fuse twice. Blows straightaway when system reset.
How can I identify what is causing the problem
Chris, July 2019
Disconnect cables at aux + and - terminals. If system resets without fuse blowing then there must be a short circuit between one of the cores. If you have a test meter check for continuity between each pair of cores in each cable. There should be no continuity if there is then that is the faulty cable/ sensor or whatever is on that zone. If no meter reconnect each cable in turn until fuse blows, faulty cable found. Much easier with a meter though!

alan mckenzie, July 2019