katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

Glow-worm kfb 50 problem?

my boiler shows only 2 neon lites on pcb and the fan will not kick in
I fear its the fan assembly unit as there is 240v to it. could anyone advise please if it could be another problem
phil gold, January 2007
If you have 240v to the fan; but the fan is not spinning then it's the fan that is at fault.

You can jump start these by using a long (8") screwdriver and "flicking" the edge of the outer impellor... This might get you heating for a couple of days - But new fan req'd.

GasAid.co.uk, January 2007