John asked ... Scantronics 9450 box stuck shut?    |    Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Click here to ask your question

potterton profile 80e?

From cold,
The fan is running ok , the pressure switch is ok ( new ) all pipes to air pressure switch are clear

Boiler begins start sequence , but stops just as fan runs , this happens for about 15/20 times then the boiler fires , then runs ok until shut down , and problem returns ant next switch on time ??
sparkey, January 2007
control board has done the trick

sparkey, February 2007
Hi, did one of these today. changed the air pressure switch, still the same problem (checked with meter and was faulty) then replaced pcb all fired up OK

Paul the gas man, January 2007