2 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

severe clicking (relay type noise)?

baxi solo 3 pf boiler (after the time clock has switched off the boiler) a few minutes later the boiler makes a load clicking noise gradually stops but very noisey , any ideas please ?
andrew dunnington, June 2007
I have come across this problem a few times, it is the relay on the pcb that controls the pump, there should be a delay after the boiler turns off before the pump stops, this is called pump overrun, intended to remove latent heat from the boiler. the control for this relay is not switching correctly and causes the relay chatter.
to remedy this problem you will need to replace the pcb

gary.wright53@googlemail.com, June 2007