2 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Variations in heat from taps and shower?

Sometimes my hot tap is too hot to use and other times it fuctuates between hot and medium when turned on full. My hot water is set at 55 which cannot be highered. The shower(Mira) set at hotest point is only fairly hot. Ferroll optimax HE 31C condensing boiler - new.
Welsh Roy, December 2008
Roy, You dont say what model Mira shower you have.
It should be a thermostatic type. It sounds like a modern boiler so ensure it has a modulating Burner / Gas valve (Ring Ferolli) It probably has . Modern thermostatic showers require the Hot supply to be 10 degrees higher than the required Blend ie what you shower in . If your hot is only 55 degrees and your showering in 46 - 48 you may not get proper control. Post a question to the corgi lads. I suspect you should have at leats 60-65 drgrees from you boiler.
Check that your supplies are not crossed on your shower valve . It should be hot on the left cold on the right. You should be able to feel. If your installer is coming back or if thats you isolate the apropriate services and remove and clean the service filters on the shower valve. Good luck

Alan, December 2008