Dan asked ... Why is Google Keep so slow on my iPhone?    |    dave s asked ... Transmission not working?    |    Tom asked ... Replace rear right door upper right latch cable - high roof?    |    ian asked ... Vaillant timeswitch 150 analogue unit (clock stopped?    |    Art Cour asked ... How do I get engine cowling off to find gas leaking?    |    Click here to ask your question

Riello burner needs reset to start?

Can the amount of time the Riello 40 F5 burner pumps the oil before ignition attempted be increased? We have an in ground oil tank which needs a while longer to get the oil to the pump. Because of this burner does not fire and the reset button needs to be pressed to start it. This only happens if air temp is not too cold and the burner is off for several hours. This way the oil has slowly gone done in the pipe.
david, March 2009
Fit a Non Return Valve in the Suction Line, with the Arrow on the Valve pointing towards the Burner, this way the oil should not fall back to the tank!

Boiler Repairman - Ipswich, April 2009