Trouble shooting guide required for Ravenheat 820/20 combi boiler?

Does anyone have a copy of this user manual/service guide/trouble shooter they could email me.

My boiler is on the blink (no hot water or central heating), luckily my father is a Corgi registered fitter (he can do pretty much everything where-as I can use a pc!) but I can't find the manual with the wiring diagrams etc. I've tried the Ravenheat webpage but it no longer lists this model.

If you can help please email on nick_king@blueyonder.co.uk

Many thanks,

Nick
Nick King, January 2006


done
hi i have a csi 85a the pump runs the fan runs the system keeps shutting down if i take the pipe off the pressure switch and i blow down it, it fires up ok there is a short pipe from switch that goes no where is this ok, does the fan cause a vacume inside the caseing may i have a loss of presure

gary davidson, February 2008
is there 240v to pump and is there 240v to fan or 90v ,ensure pressure is above 1 bar , remove hose from air pressure switch and suck whilst calling for heat, if the boiler fires and there is 90-110v on the fan it is your circuit board,

mike, January 2006
is there 240v to pump and is there 240v to fan or 90v

mike, January 2006
Mike, do you need anymore information?

Cheers,

Nick.

Nick King, January 2006
on call for heat or hot water there is power to boiler but ignition sequence does not start it has a permanent pilot [fan runs on low speed] but does not increase speed nor does pump run all fuses on PCB ok

john [Nicks Dad], January 2006
no literature but give me somemore specific details of fault and ill help your dad fix it does boiler start ignition sequence? how far into it does it get more info please

mike, January 2006