Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

no hot water sime super 90?

when i run my hot water tap slow the water goes cold and the boiler cuts out
alan, October 2010
A combi boiler requires a certain flow rate at the tap to stop boiler from overheating and cutting out. So by cutting back your tap to slow , you are not allowing this and the boiler is cutting out. Open your taps more to allow a good flow rate, if water not warm enough then flow rates have to be adjusted by gas boiler engineer. If this doesn't help u have a diverter valve problem.

simeservicesscotland.com, October 2010