Tom asked ... Service manual for Lawnflite 908LA?    |    John asked ... Scantronics 9450 box stuck shut?    |    Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Click here to ask your question

boiler lock out glow worm beta com 30c?

boiler locked out pressure at 1.5 bars. condenser sensor is dryer. no water in condenser or pipe.boiler fires up for 10 seconds then red light flashes and boiler cuts out.i have reset many times and this still happens.fan is running ok. anyone got any suggestions or do I call a gas man out.thank you
gwen, March 2014
I called out a gas man.he looked and checked condenser senser. got my hair dryer warmed it up (warm not hot) turned boiler back on and it started straight away.nice man didn't charge me just a drink.hope this helps someone so simple but so much stress.

gwen, March 2014